Boiler Water Treatment: From Feedwater to Condensate
6 min read·
boilerfeedwatercondensateoxygen-scavenger
Boiler Water Treatment Stages
| Stage | Chemical | Purpose |
|---|---|---|
| Feedwater deaeration | Mechanical deaerator + chemical O₂ scavenger | Remove dissolved O₂ to < 7 ppb |
| Internal treatment | Phosphate or all-volatile treatment | Prevent scale on boiler tubes |
| Condensate protection | Filming amine or neutralizing amine | Prevent CO₂/O₂ corrosion in return lines |
| Blowdown | Controlled continuous + intermittent | Maintain TDS/alkalinity within limits |
Oxygen Scavenger Selection
| Scavenger | Boiler Pressure | FDA Steam | Reaction Speed | Cost |
|---|---|---|---|---|
| Sodium sulfite | < 60 bar | No (adds TDS) | Fast | Lowest |
| Hydrazine | > 60 bar | No (carcinogen) | Slow below 150°C | Medium |
| Carbohydrazide | All pressures | Yes | Medium | Higher |
| DEHA | 40–100 bar | Yes | Fast at low temp | Higher |
Key rule: Always maintain measurable O₂ scavenger residual in feedwater (5–20 ppm sulfite, or 50–100 ppb hydrazine equivalent).
Internal Treatment Programs
Coordinated phosphate treatment (most common for medium-pressure):
- Trisodium phosphate: Maintain 5–15 ppm PO₄ in boiler water
- pH control: 9.5–10.5 in boiler water
- Prevents CaCO₃ and CaSO₄ scale by converting to soft hydroxyapatite sludge
All-volatile treatment (AVT) for high-pressure (> 100 bar):
- Ammonia or morpholine for pH control (pH 9.0–9.6)
- No phosphate — avoids solid deposits
- Requires ultra-pure feedwater (conductivity < 0.3 µS/cm)
Condensate Protection
CO₂ from bicarbonate decomposition dissolves in condensate → carbonic acid → corrosion.
Two approaches:
- Neutralizing amines (morpholine, cyclohexylamine): Neutralize carbonic acid, raise pH to 8.5–9.0
- Filming amines (octadecylamine): Form hydrophobic barrier on pipe walls
Monitoring
| Parameter | Where | Target |
|---|---|---|
| Dissolved O₂ | Deaerator outlet | < 7 ppb |
| O₂ scavenger residual | Feedwater | 5–20 ppm (sulfite) |
| pH | Boiler water | 9.5–10.5 |
| Phosphate (PO₄) | Boiler water | 5–15 ppm |
| Conductivity | Boiler water | Per OEM limits |
| Iron | Condensate | < 20 ppb |
| pH | Condensate | 8.5–9.0 |