Cooling Water Treatment Chemical Program Design

6 min read·
cooling-waterscalecorrosionbiocide

The Three Pillars

Every cooling water program must address three threats simultaneously:

  1. Scale — mineral deposits on heat transfer surfaces
  2. Corrosion — metal loss from pipes and heat exchangers
  3. Microbiological growth — biofilm, algae, Legionella

Scale Control Program

Scale TypePrimary InhibitorDosageNotes
CaCO₃HEDP or PBTCA2–5 ppmPBTCA preferred if using chlorine
CaSO₄ATMP or AA/AMPS3–8 ppmHigher dose needed at high hardness
SilicaPolymer dispersant5–15 ppmCritical when SiO₂ > 150 ppm in makeup

Corrosion Control Program

MetalInhibitorDosageMechanism
Mild steelHEDP + zinc sulfate2–5 ppm HEDP + 1–2 ppm ZnAnodic + cathodic protection
Copper alloysTolyltriazole (TTA)1–3 ppmForms Cu-TTA film
Stainless steelMolybdate (if needed)50–100 ppm MoO₄For closed systems

Biocide Program

Combine oxidizing + non-oxidizing biocides:

  • Continuous: SDIC or TCCA tablets at 0.3–0.5 ppm free chlorine residual
  • Shock: DBNPA 50 ppm or glutaraldehyde 100 ppm, 2–3x per week
  • Legionella control: Maintain > 0.5 ppm free chlorine at all times

Monitoring Parameters

ParameterFrequencyTarget
pHDaily7.0–9.0
Conductivity/TDSDaily< 2500 µS/cm (varies by CoC)
Free chlorineDaily0.3–0.5 ppm
HEDP/phosphonate residualWeekly2–5 ppm
Iron (corrosion indicator)Weekly< 1 ppm
Bacteria countMonthly< 10⁴ CFU/mL

Blowdown Control

Cycles of concentration (CoC) = Makeup conductivity / Blowdown conductivity. Target 3–5 CoC for most systems. Higher CoC saves water but increases scaling risk.