Cooling Water Treatment Chemical Program Design
6 min read·
cooling-waterscalecorrosionbiocide
The Three Pillars
Every cooling water program must address three threats simultaneously:
- Scale — mineral deposits on heat transfer surfaces
- Corrosion — metal loss from pipes and heat exchangers
- Microbiological growth — biofilm, algae, Legionella
Scale Control Program
| Scale Type | Primary Inhibitor | Dosage | Notes |
|---|---|---|---|
| CaCO₃ | HEDP or PBTCA | 2–5 ppm | PBTCA preferred if using chlorine |
| CaSO₄ | ATMP or AA/AMPS | 3–8 ppm | Higher dose needed at high hardness |
| Silica | Polymer dispersant | 5–15 ppm | Critical when SiO₂ > 150 ppm in makeup |
Corrosion Control Program
| Metal | Inhibitor | Dosage | Mechanism |
|---|---|---|---|
| Mild steel | HEDP + zinc sulfate | 2–5 ppm HEDP + 1–2 ppm Zn | Anodic + cathodic protection |
| Copper alloys | Tolyltriazole (TTA) | 1–3 ppm | Forms Cu-TTA film |
| Stainless steel | Molybdate (if needed) | 50–100 ppm MoO₄ | For closed systems |
Biocide Program
Combine oxidizing + non-oxidizing biocides:
- Continuous: SDIC or TCCA tablets at 0.3–0.5 ppm free chlorine residual
- Shock: DBNPA 50 ppm or glutaraldehyde 100 ppm, 2–3x per week
- Legionella control: Maintain > 0.5 ppm free chlorine at all times
Monitoring Parameters
| Parameter | Frequency | Target |
|---|---|---|
| pH | Daily | 7.0–9.0 |
| Conductivity/TDS | Daily | < 2500 µS/cm (varies by CoC) |
| Free chlorine | Daily | 0.3–0.5 ppm |
| HEDP/phosphonate residual | Weekly | 2–5 ppm |
| Iron (corrosion indicator) | Weekly | < 1 ppm |
| Bacteria count | Monthly | < 10⁴ CFU/mL |
Blowdown Control
Cycles of concentration (CoC) = Makeup conductivity / Blowdown conductivity. Target 3–5 CoC for most systems. Higher CoC saves water but increases scaling risk.